CU / XLPE / CTS / PVC Cable, 6/10kV 8.7/15kV 12/20kV 18/30kV

CU / XLPE / CTS / PVC Cable, 6/10kV 8.7/15kV 12/20kV 18/30kV
CU / XLPE / CTS / PVC Cable, 6/10kV 8.7/15kV 12/20kV 18/30kV
Request a Quote

Medium voltage single core cable is suitable for use in power networks, in fixed installation outdoors in cable ducts or directly in the ground. Cable operational stability is enhanced because of very low dielectric loss factor, excellent insulation property of XLPE and firm bonding with conductor screen and insulation screen of semi-conductive material (extruded in one process), which makes it widely used in transformer stations, electric power plants and industrial plants.

Construction

1)Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
2)Conductor screen: Non-metallic, semi-conducting compound
3)Insulation: Cross-linked polyethylene XLPE
4)Insulation screen: Non-metallic, semi-conducting compound
5)Metallic screen: Copper tape
6)Outer sheath: Polyvinyl chloride PVC

Specifications
IEC 60228 Conductors
IEC 60502-2 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 2: Cables for rated voltages of 6 kV(Um=7.2kV) and 30 kV(Um=36kV)

Parameters

Single Core Cable - 6/10kV and 8.7/15kV
No. of cores and nominal cross section Thickness of insulation Thickness of sheath Approx. overall diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In air (A) In ground (A)
YJV (N2XSY) - 6/10kV
1X16 3.4 1.8 18.5 486 1.15 130 145
1X25 3.4 1.8 19.5 594 0.727 170 190
1X35 3.4 1.8 20.5 706 0.524 205 225
1X50 3.4 1.8 21.8 849 0.387 245 270
1X70 3.4 1.8 23.5 1078 0.268 310 335
1X95 3.4 1.8 25.1 1351 0.193 380 405
1X120 3.4 1.8 26.5 1605 0.153 435 460
1X150 3.4 1.8 28.0 1880 0.124 495 520
1X185 3.4 1.9 29.9 2269 0.0991 570 585
1X240 3.4 2.0 32.3 2840 0.0754 680 690
1X300 3.4 2.0 34.5 3427 0.0601 780 775
1X400 3.4 2.1 37.7 4259 0.0470 910 890
1X500 3.4 2.2 40.8 5330 0.0366 1060 1010
1X630 3.4 2.3 44.8 6703 0.0283 1230 1130
YJV (N2XSY) - 8.7/15kV
1X25 4.5 1.8 21.7 677 0.727 170 190
1X35 4.5 1.8 22.7 793 0.524 205 225
1X50 4.5 1.8 24.0 940 0.387 245 270
1X70 4.5 1.8 25.7 1175 0.268 310 335
1X95 4.5 1.8 27.3 1454 0.193 380 405
1X120 4.5 1.9 28.9 1726 0.153 435 460
1X150 4.5 1.9 30.4 2006 0.124 495 520
1X185 4.5 2.0 32.3 2403 0.0991 570 585
1X240 4.5 2.0 34.5 2969 0.0754 680 690
1X300 4.5 2.1 36.9 3580 0.0601 780 775
1X400 4.5 2.2 40.1 4425 0.0470 910 890
1X500 4.5 2.3 43.2 5509 0.0366 1060 1010
1X630 4.5 2.4 47.2 6898 0.0283 1230 1130
Single Core Cable - 12/20kV and 18/30kV
No. of cores and nominal cross section Thickness of insulation Thickness of Sheath Approx. overall diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In air (A) In ground (A)
YJV (N2XSY) - 12/20kV
1X35 5.5 1.8 25.46 896 0.524 150 225
1X50 5.5 1.8 26.76 1080 0.387 180 270
1X70 5.5 1.8 28.46 1319 0.268 220 330
1X95 5.5 1.9 30.26 1613 0.193 265 400
1X120 5.5 2.0 31.66 1887 0.153 310 460
1X150 5.5 2.0 33.46 2229 0.124 350 520
1X185 5.5 2.1 35.06 2602 0.0991 400 585
1X240 5.5 2.1 37.66 3200 0.0754 465 680
1X300 5.5 2.2 39.86 3832 0.0601 535 775
1X400 5.5 2.3 43.26 4872 0.0470 615 885
1X500 5.5 2.4 47.14 5928 0.0366 725 1000
YJV (N2XSY) - 18/30kV
1X35 8.0 1.9 30.1 1134 0.524 238 172
1X50 8.0 2.0 31.3 1294 0.387 286 203
1X70 8.0 2.0 33.2 1560 0.268 356 246
1X95 8.0 2.1 35.0 1870 0.193 434 293
1X120 8.0 2.1 36.4 2152 0.153 500 332
1X150 8.0 2.2 37.9 2468 0.124 559 366
1X185 8.0 2.2 39.7 2875 0.0991 637 410
1X240 8.0 2.3 42.3 3497 0.0754 745 470
1X300 8.0 2.4 44.6 4145 0.0601 846 524
1X400 8.0 2.5 47.5 5020 0.047 938 572
1X500 8.0 2.6 50.9 6156 0.0366 1065 725