Steel Crossflow Cooling Tower (Low Noise)

Steel Crossflow Cooling Tower (Low Noise)
Request a Quote

The steel crossflow cooling tower’s casing is made of all-steel material. This cooling tower series features a low noise, and are environmentally friendly. Even after the service life, the steel material remains recyclable and environmentally friendly as it causes no pollution. The lowest noise levels of this heat rejection device is only 58.5db. For areas where environmental requirements are relatively high, then we recommend the following standard cooling tower systems. If these models do not meet your needs, please contact us about customization services.

Design condition
  • Inlet water temperature: T1=37℃
  • Outlet water temperature: T2=32℃
  • Wet bulb temperature: TWB=28℃
  • Dry bulb temperature: T=31.5℃
Level Model Overall dimension (mm) Flow rate (m3/h) Fan (φ) mm Motor (Kw) Weight (Kg) Noise (dB)
L W H Net weight (DRY) Running weight (Wet)
LRTS-100L/S 2000 3250 3700 100 1470 3 1055 1670 58.5
LRTS-125L/S 2600 3550 3700 125 1800 4 1160 2680 59.5
LRTS-150L/S 3000 3850 3700 150 2100 4 1290 2890 60.5
LRTS-175L/S 3000 3850 4200 175 2100 5.5 1410 3210 61
LRTS-200L/S 3200 4130 4200 200 2400 5.5 1550 3640 61.5
LRTS-225L/S 3200 4130 4750 225 2400 5.5 1710 3800 61.5
LRTS-250L/S 2880 4890 4200 250 2400 7.5 2400 4600 62
LRTS-300L/S 3450 5480 4200 300 3000 11 2600 5660 62.5
LRTS-350L/S 3450 5480 4750 350 3000 11 2870 6000 63
LRTS-400L/S 4300 5890 4400 400 3330 15 3270 6710 63.5
LRTS-450L/S 4300 5890 4950 450 3330 15 3680 7370 63.8
Related products
Send Message
Inquiry
Inquiry