Steel Crossflow Cooling Tower (Ultra Low Noise)
Request a Quote
The steel crossflow cooling tower is made of all-steel material, which ensures it is corrosion resistant. This series of evaporative cooling towers are environmentally-friendly and cause no pollution to the environment, because the steel materials are recyclable, even if the cooling tower is past its service life. This cooling tower system features a low noise level that is controlled to within 57db. If the application environment has strict environmental requirements, our standard cooling systems are all ideal. If the standard models do not meet your needs, please do not hesitate to contact us about customization services.
Design condition
- Inlet water temperature: T1=37℃
- Outlet water temperature: T2=32℃
- Wet bulb temperature: TWB=28℃
- Dry bulb temperature: T=31.5℃
- Atmospheric pressure: P=9.94×104 Pa
Level Model | Overall dimension | Flow rate (m3/h) | Fan φ (mm) | Motor (Kw) | Weight (Kg) | Noise (dB) | |||
L | W | H | Net weight (DRY) | Running weight (Wet) | |||||
LRTS-100UL/S | 2000 | 3250 | 4400 | 100 | 1470 | 3 | 1055 | 1670 | 57 |
LRTS-125UL/S | 2600 | 3550 | 4400 | 125 | 1800 | 4 | 1160 | 2680 | 58 |
LRTS-150UL/S | 3000 | 3850 | 4400 | 150 | 2100 | 4 | 1290 | 2890 | 59 |
LRTS-175UL/S | 3000 | 3850 | 4900 | 175 | 2100 | 5.5 | 1410 | 3210 | 59 |
LRTS-200UL/S | 3200 | 4130 | 4900 | 200 | 2400 | 5.5 | 1550 | 3640 | 60 |
LRTS-225UL/S | 3200 | 4130 | 5450 | 225 | 2400 | 5.5 | 1710 | 3800 | 60 |
LRTS-250UL/S | 2880 | 4890 | 4900 | 250 | 2400 | 7.5 | 2400 | 4600 | 60.5 |
LRTS-300UL/S | 3450 | 5480 | 4900 | 300 | 3000 | 11 | 2600 | 5660 | 61 |
LRTS-350UL/S | 3450 | 5480 | 5450 | 350 | 3000 | 11 | 2870 | 6000 | 61.5 |
LRTS-400UL/S | 4300 | 5890 | 5100 | 400 | 3330 | 15 | 3270 | 6710 | 62 |
LRTS-450UL/S | 4300 | 5890 | 5650 | 450 | 3330 | 15 | 3680 | 7370 | 62.3 |
Related products
Send Message
Most Recent
More
Other Products
Videos