FRP Counterflow Cooling Tower (Low Noise)
Request a Quote
FRP counterflow cooling towers feature a low noise level and counterflow design for circulating water. We offer this cooling tower in a variety of models, ranging in 80m3/h~1000m3/h of circulating water for customers to choose from. Users can choose the right evaporative cooling products for their needs according to specific requirements, and in doing so, save energy consumption and occupied area to further save costs. For more information, pleases see the following standard products. We also offer customization services for specific requirements.
Design condition
- Inlet water temperature: T1=37℃
- Outlet water temperature: T2=32℃
- Wet bulb temperature: TWB=28℃
- Dry bulb temperature: T=31.8℃
- Atmospheric pressure: P=9.94×104 Pa
Selection table of low noise type counterflow cooling towers
Model | Overall dimension (mm) | Flow rate (m3/h) | Fan Φ (mm) | Motor (Kw) | Weight (Kg) | Noise (dB) | ||||||
Standard type | Low noise type | Standard type | Low noise type | |||||||||
L | W | H | ||||||||||
Dry | Wet | Dry | Wet | |||||||||
LRN-80L/S | 2580 | 2580 | 4330 | 80 | 1470 | 3 | 960 | 2060 | 1060 | 2160 | 62 | 60.5 |
LRN-100L/S | 2770 | 2770 | 4330 | 100 | 1800 | 3 | 1140 | 2330 | 1260 | 2450 | 62 | 60.5 |
LRN-125L/S | 2920 | 2920 | 4330 | 125 | 1800 | 4 | 1310 | 2600 | 1440 | 2730 | 62.5 | 61 |
LRN-150L/S | 3120 | 3120 | 4330 | 150 | 2000 | 4 | 1550 | 2980 | 1700 | 3130 | 63 | 61.5 |
LRN-175L/S | 3120 | 3120 | 4430 | 175 | 2000 | 5.5 | 1830 | 3230 | 1980 | 3380 | 63 | 61.5 |
LRN-200L/S | 3320 | 3320 | 4430 | 200 | 2200 | 5.5 | 2140 | 3700 | 2320 | 3880 | 64 | 62.5 |
LRN-225L/S | 3520 | 3520 | 4430 | 225 | 2400 | 7.5 | 2450 | 4170 | 2670 | 4390 | 64.5 | 63 |
LRN-250L/S | 3520 | 3520 | 4530 | 250 | 2400 | 7.5 | 2530 | 4250 | 2750 | 4470 | 64.5 | 63 |
LRN-300L/S | 4120 | 4120 | 4730 | 300 | 3000 | 11 | 2850 | 5520 | 3160 | 5830 | 65 | 63.5 |
LRN-350L/S | 4120 | 4120 | 4930 | 350 | 3000 | 11 | 2970 | 5640 | 3380 | 6050 | 65 | 63.5 |
LRN-400L/S | 4610 | 4610 | 4980 | 400 | 3400 | 15 | 3510 | 6700 | 3830 | 7020 | 65.5 | 64 |
LRN-450L/S | 4910 | 4910 | 5080 | 450 | 3400 | 15 | 3660 | 6850 | 3980 | 7170 | 65.5 | 64 |
LRN-500L/S | 5230 | 5230 | 5300 | 500 | 3700 | 15 | 4250 | 8150 | 4650 | 8550 | 66.5 | 65 |
LRN-600L/S | 5600 | 5600 | 5500 | 600 | 3700 | 18.5 | 4690 | 8590 | 5090 | 8990 | 66.5 | 65 |
LRN-700L/S | 6000 | 6000 | 5600 | 700 | 4200 | 22 | 5680 | 10100 | 6350 | 10770 | 67 | 65.5 |
LRN-800L/S | 6300 | 6300 | 6100 | 800 | 4200 | 22 | 6630 | 11700 | 7300 | 12370 | 67 | 65.5 |
LRN-900L/S | 6930 | 6930 | 6600 | 900 | 4500 | 30 | 7680 | 14300 | 8400 | 15020 | 68 | 67 |
LRN-1000L/S | 7430 | 7430 | 6600 | 1000 | 4500 | 30 | 8630 | 16100 | 9230 | 16700 | 68 | 67 |
Note:
The above table shows technical parameters of the single fan cooling towers. Each model can be used individually, or in a combination as needed.