Refrigerated Compressed Air Dryer

Refrigerated Compressed Air Dryer
Request a Quote

Refrigerated compressed air dryers are designed with a highly efficient refrigerant compressor and refrigerant accessories. With a pressure drop in the airflow channel at less than 0.02Mpa, the working efficiency is improved and electricity usage is reduced.

Working condition
  • Inlet temperature Lower than 70℃ (high temperature); lower than 45℃ (low temperature)
  • Working pressure 6~10kg/cm²
  • Maximum pressure 1.0Mpa, 10kg/cm² (customized pressure is available)
  • Environment temperature 2~50℃
  • Refrigerant R22 (R407c, R134a customized refrigerant is provided)
  • Dew point temperature 2~10℃ (when air pressure is 7kg/cm²)
Advantages
  • Refrigerated compressed air dryers use a high quality thermal expansion valve, which is able to automatically adjust refrigerant supply according to the dryer's actual load, making the air compressor more energy saving and energy efficient.
  • This air dryer is designed with a superior electronic drain valve, which, after being set, can discharge the moisture accumulated in the compressed air in time, ensuring the dryness of the compressed air.
  • The heat exchanger in the refrigerant compressed air dryer uses an 8mm thick copper pipe, ensuring the heat exchanger remains crack free.
  • The filter in the air dryer features a small volume and large filtration area, which can filter moisture and impurities in the cooling system, making the air dryer cleaner and less prone to failure frequencies.
  • The refrigerant compressed air dryer is able to automatically detect low oil pressures in the semi-hermetic compressor to make it more reliable and safe.
Optional models
Model Handling capacity (m3/min) Air volume SCFM Overall power (KW) Power supply(V) Inlet and outlet size Dimension H×W×D(mm) Approximate net weight kg
FD20 1.2 43 0.79 1ph 220VAC G3/4" 620×280×660 46
FD30 1.8 63 0.81 650×280×660 52
FD40 2.4 88 0.86 G1" 760×340×720 70
FD60 3.6 135 0.88 G11/2" 840×380×800 77
FD120 7.2 240 1.5 940×500×930 125
FD180 10.8 317 2.39 G21/2" 1040×540×1100 180
FD250 15 459 2.7 3ph 380VAC 1040×560×1330 230
FD300 18 635 3.35 DN80 1080×630×1400 255
FD400 24 812 4.3 1200×710×1500 320
FD450 27 987 5.2 1200×710×1500 370
FD600 36 1200 6.8 DN100 1350×900×1650 550
FD750 45 1588 8.8 DN125 1500×1900×1000 560
FD850 51 1925 10.7 1600×2100×1100 600
(Models with other voltage can be customized)
Notes
  • In the specification chart, "G" stands for "screw threaded connection", while the "DN" stands for "nominal diameter of flange connection".
  • There should be no less than 1m space left around the dryer unit for ventilation and maintenance. The dryer unit can be easily installed without the base.
  • The stop valve must be installed in the dryer unit inlet and outlet. A bypass valve should also be mounted in the unit under the condition that the air displacement is not interrupted. This makes it easier to repair and maintain the equipment.
  • If the model, parameters, specifications and colors of the air dryer changes, please refer to the machine for actual data.
  • The rated air handling capacity should be adjusted when the working temperature and pressure exceeds the specified requirements.
  • Atlas Greenair is able to provide customized air dryers with various specifications.