Meters and Measurement Devices for Exact Consumption Data Acquisition

Meters and Measurement Devices for Exact Consumption Data Acquisition
Meters and Measurement Devices for Exact Consumption Data Acquisition
Request a Quote

This multifunctional power meter is a three-phase four-wire smart power meter, specially designed for the electrical power monitoring and control demands in power supply and distribution systems. This power meter measures active and reactive energy and all the common electric power parameters, including three-phase voltage, three-phase-current, active power, and more. In addition, this meter also features a number of features, including the accumulation of electric energy, electric energy pulse output, limit alarm, input and on-off output, transmitting output of analog, network communication and much more.

Application
Multifunctional power meters are applicable to a variety of control systems, energy management systems, substation automation, distribution network automation, industrial automation, intelligent building, distribution boxes and switch cabinets.

Measuring range
  • Three-phase voltage: UA UB UC;UAB UBC UCA
  • Three-phase current: IA IB IC
  • Active power: single-phase active power and total active power
  • Reactive power: single-phase reactive power and total reactive power
  • Apparent power: single-phase apparent power and total apparent power
  • Power factor: single-phase power factor and total power factor
  • Line frequency
  • Electrical energy: active energy, reactive energy
  • Two electric energy pulse outputs
  • Four analog outputs
  • Four on-off outputs
  • Four on-off inputs
Technical parameters
Panel size 96×96mm
Hole size 91×91mm
Installation Insertion
Communication interface RS485
Communication protocol MODBUS-RTU
Communication baud rate Factory default: 9600bpS (1200bps-9600bpsoptional)
Operating power supply AC220V
Power consumption 5VA
Input measuring voltage Rated value AC100 or AC400
Overload Continuous: 1.2 times; instaneous: 10 times/10s
Power consumption Single-phase: 1VA
Impedance 500KΩ
Accuracy RMS measurement, accuracy class 0.5
Input measuring current Rated value AC1A or AC5A
Overload Continuous: 1.2 times; instaneous: 10 times/10s
Power consumption Single-phase: 0.4VA
Impedance 2MΩ
Accuracy RMS measurement, accuracy class 0.5
Two electric energy pulse outputs 3200imp/kwh
Display LCD
Withstand voltage input/power supply>2KV, input/output>2KV, power supply/output>2KV
Insulation 50MΩ
Working environment -10~55℃
Storage environment -20~75℃
Outline sizes