Earthing Switch (JN15 Indoor High Voltage Earthing Switch)
- JN15-12 Earthing Switches
- JN15-24 Earthing Switches
- JN15-40.5 Earthing Switches
Introduction
The JN15 earthing switch is our world-advanced new development designed in reference to the EK6 earthing switch of German GALOR-EMAG company. It has advantages of cutting-edge design, reliable performance, simple structure and ease of mounting and commissioning. The performance not only meets GB1985-2004 requirements, but also complies with German DINVDE670 and IEC129 standards. As a type of electrical components, the indoor high voltage earthing switch works with ABB-UniGear ZS1, ZS2, Siemens-NXAIR, Schneider-Nvnex and Tellhow-KYN28A type medium voltage switchgear.
Service Conditions
1) Altitude: ≤1000m
2) Ambient air temperature: up to 40 ℃, down to -10 ℃, daily range of 15 ℃
3) Humidity: daily average relative humidity less than 95%; monthly average relative humidity less than 90%
4) Earthquake intensity: ≤ 8 degrees
1. □- Pole-center distance
2. □- Rated short time withstand current (KA)
3. □- Rated voltage (KV)
4. 15 - Design number
5. N-Indoor
6. J-Earthing switch Technical Parameters
Rated voltage (KV) | 12 | 24 | 40.5 |
Rated short time withstand current (KA) | 31.5, 40, 50 | 31.5 | 31.5 |
Rated short circuit duration (S) | 4 | 4 | 4 |
Rated peak withstand current (KA) | 80, 100, 125 | 80 | 80 |
Rated short-circuit making current (KA) | 80, 100, 125 | 80 | 80 |
Pole-center distance (mm) | 165,180,200,210,220,230,250,275 | 210,265,275 | 280,300,350,400,440 |
Rated 1min power frequency withstand voltage (KV) | 42 | 65 | 95 |
Rated lightning impulse withstand voltage (KV) | 75 | 125 | 185 |
Mechanical life (cycles) | 2000 | 2000 | 2000 |
Outline and Mounting Dimension
JN15-12 Earthing Switches